SWITCHGEAR WITH HORIZONTAL ISOLATION TYPE AH12 (SINGLE BUSBAR)

Type AH12 Air Insulated Switchgear Panels are equipped with horizontal draw out, horizontal isolation type switchgear device (VCB / VC) up to breaking capacity of 50kA.
TECHNICAL DATA FOR AH12 | |
---|---|
Voltage | Up to 12kV 50Hz |
Unit Rating | Up to 3150A / 4000A |
Bus Bar Rating | Up to 4000A |
Short Time Current | Up to 50kA for 3 second |
P.F. Withstand | Up to 38kV |
Impulse Withstand | Up to 95kVp |
Internal Arc Classification | AFLR Up to 50kA – 1 second |
Applicable Standards | IEC 62271-200 |
TECHNICAL DATA FOR VC | |
---|---|
Rated Voltage | Up to 7.2kV |
Rated Thermal current | Up to 400A |
Mechanism | Electrically latched / Mechanically latched |
Utilization Category | AC4 |
Breaking Capacity | Up to 6kA 40kA (with fuse) |